Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T05CM02790
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2006 | REINFORCED MASONRY PRE-GROUT | Approved | ||
03/15/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* (4'4"-8'4") |
|
03/14/2006 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* 1. NEED 3/4 ANCHOR BOLTS @ LEDGER 2. NEED ADDITIONAL VERTICAL REBAR ABOVE DOOR OPENING TO MAINTAIN 32" O.C. SPACING 3. NEED SPECIAL INSPECTION PLEASE HAVE SPECIAL PROVIDE THE HEIGHTS OR LIFT @ THAT SPECIAL INSPECTION. |
|