Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T05CM02768

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2005 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/04/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
NO MESSAGE!
1. NO SUPT. ON JOB
2. UNABLE TO LOCATE CONDENSATE PUMP,
ADDRESSED BY 7/11/05 MECH. INSP. THIS IS NOT INDICATED ON SHEET R3 OF APP. PLAN?
RECALL W/PHONE NUMBER SO PROBLEM CAN BE DISCUSSED.
07/11/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT CONDENSATE PUMP FROM STRUCTURE NOT FROM PVC DRAIN PIPE
2) INSTALL OVERFLOW DEVICE
3) PROVIDE INSTRUCTIONS FOR CONDENSATE PUMP
4) NEED TO SEE HOW FAR IT WILL PUMP