Permit: T05CM02754

Parcel: 106120530

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/21/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED ARC FAULT IN BEDROOM LIGHTING CKT
GO THROUGH THIS LIST AND LIST FOR T05CM02753
10/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CORRECTLY IDENTIFY UNITS @ SERVICE.
2. REPLACE SERVICE DISCONNECT COVERS
3. IDENTIFY SERVICE DISCONNECTS
4. MULTI-WIRE BRANCH CKTS NEED TO BE ON SEPARATE PHASES.
5. STRAP WATER HEATER FLEX AND TERMINATE GROUND PROPERLY.
6. 3-WAYS ON LIGHTING NOT WORKING
7. SECURE ROMEX TO PEN. RECEPTACLE.
8. CEILING FANS NOT WORKING.
9. NITCH LIGHT UPSTAIRS?
10. ALL SWITCHES TO BE GROUNDED WITH EQUIPMENT GROUND.
11. MAKE SURE PANELS ARE CORRECTLY IDENTIFIED.
12. AC UNITS NOT IN YET

INSPECTIONS FOR 32101 ONLY -- GO THROUGH ALL UNITS AND CHECK FOR THESE AND OTHER PROBLEMS.
08/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) HAVE PANEL COVERS OPEN FOR INSPECTION
2) CALL AFTER ENERGIZED AND ELECTRICIAN HAS GONE THROUGH INSTALLATION