| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED ARC FAULT IN BEDROOM LIGHTING CKT GO THROUGH THIS LIST AND LIST FOR T05CM02753 |
|
| 10/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECTLY IDENTIFY UNITS @ SERVICE. 2. REPLACE SERVICE DISCONNECT COVERS 3. IDENTIFY SERVICE DISCONNECTS 4. MULTI-WIRE BRANCH CKTS NEED TO BE ON SEPARATE PHASES. 5. STRAP WATER HEATER FLEX AND TERMINATE GROUND PROPERLY. 6. 3-WAYS ON LIGHTING NOT WORKING 7. SECURE ROMEX TO PEN. RECEPTACLE. 8. CEILING FANS NOT WORKING. 9. NITCH LIGHT UPSTAIRS? 10. ALL SWITCHES TO BE GROUNDED WITH EQUIPMENT GROUND. 11. MAKE SURE PANELS ARE CORRECTLY IDENTIFIED. 12. AC UNITS NOT IN YET INSPECTIONS FOR 32101 ONLY -- GO THROUGH ALL UNITS AND CHECK FOR THESE AND OTHER PROBLEMS. |
|
| 08/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HAVE PANEL COVERS OPEN FOR INSPECTION 2) CALL AFTER ENERGIZED AND ELECTRICIAN HAS GONE THROUGH INSTALLATION |