Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE ARC FAULT PROTECTION FOR ALL RECEPTACLES, LIGHTS AND SMOKE DETECTORS IN BEDROOMS. 2. MULTI-WIRE BRANCH CKT'S NEED TO BE ON SEPARATE PHASES. 3. NEED 12GA WIRE ON 20 AMP CKT (KITCHEN SINK LIGHT) 4. TERMINATE WATER HEATER GROUND AT FACTORY PROVISION - NOT 2 UNDER SAME SCREW. 5. INSTALL FIRE BELL LOCKOUT. |
|
| 10/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE LIST FOR T05CM02754 |
|
| 08/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HAVE PANEL COVERS OPEN FOR INSPECTION 2) CALL AFTER ENERGIZED AND ELECTRICIAN HAS GONE THROUGH INSTALLATION |