Permit: T05CM02753

Parcel: 106120530

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/21/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROVIDE ARC FAULT PROTECTION FOR ALL RECEPTACLES, LIGHTS AND SMOKE DETECTORS IN BEDROOMS.
2. MULTI-WIRE BRANCH CKT'S NEED TO BE ON SEPARATE PHASES.
3. NEED 12GA WIRE ON 20 AMP CKT (KITCHEN SINK LIGHT)
4. TERMINATE WATER HEATER GROUND AT FACTORY PROVISION - NOT 2 UNDER SAME SCREW.
5. INSTALL FIRE BELL LOCKOUT.
10/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE LIST FOR T05CM02754
08/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) HAVE PANEL COVERS OPEN FOR INSPECTION
2) CALL AFTER ENERGIZED AND ELECTRICIAN HAS GONE THROUGH INSTALLATION