Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/02/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL WARNING RIBBON FOR SERVICE CONDUCTORS NEC 300.5 2. INSTALL PERMANENT ADDRESS AND UNIT # LABELS 3. BOND SERVICE RISER NEC 250.92, NEC 250.102 (C) *GROUND RODS REPLACED CUT UFER |