Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/08/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE DELTA 1 NOTE ON SHEET E 1.1 ALL WORK IN PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13. REGULER MC CABLE NOT APPROVED FOR PATIENT CARE AREAS MUST BE GREEN TYPE H. 2) FIXTURE MISSING RESTROOM ( HANDICAP TYPE) 3) GUTTER MISSING COVER. 4) NECT ART 800 REQUIRES COMMUNICATION CABLE TO BE REMOVED TIED UP OFF CEILING AND SUPPORTED IN NEW AND EXISTING REMODELS. |