Permit: T05CM02746

Parcel: 10510062G

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/01/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/08/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. SEE DELTA 1 NOTE ON SHEET E 1.1 ALL WORK IN PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13. REGULER MC CABLE NOT APPROVED FOR PATIENT CARE AREAS MUST BE GREEN TYPE H. 2) FIXTURE MISSING RESTROOM ( HANDICAP TYPE) 3) GUTTER MISSING COVER. 4) NECT ART 800 REQUIRES COMMUNICATION CABLE TO BE REMOVED TIED UP OFF CEILING AND SUPPORTED IN NEW AND EXISTING REMODELS.