Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM02738
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/25/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK STUD FRAME WALL 2) RECEIVED M/C LETTER 3) SUPPORT BOX ABOVE CEILING AS PER 300.11 2) FINISH PREVIOUS NOTE FOR FINAL |
|
07/21/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) THHN IS NOT AN SUPPORTED METHOD 2) PLANS CALL FOR CONDUIT. PLEASE PROVIDE A LETTER AUTHORIZING USEAGE OF M/C CABLES 3) WHAT ARE CABLES, FLEX AND CONDUIT HANGING OUT OF CEILING 4) PLEASE OPEN AREAS ABOVE NEW CUT-IN BOXES TO INSPECT 5) NOTE: ARTICLE 725.6 & 800.6 AND 725.2 & 800.2 WILL APPLY |