Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM02717

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2005 FRAMING Approved IVRS - Inspection :*
11/14/2005 FRAMING Partial Approval IVRS - Inspection :*
11/09/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL 1ST AND 2ND FLOOR PENETRATIONS AT TOP OF STAIRS FOR MEDIA WIRES AND IN MASTER CLOSET
11/07/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE STAPLES BEHIND HOMERUNS
2) STRAP NON-CABIN TIED TOP PLATES OVER FRONT DOOR
3) TIGHTEN HOLDOWNS
4) FHA STRAP TOP PLATES AT STOVE VENT
5) SHIM TRIMMERS/HEADERS WHERE NEEDED
6) FIREBLOCK FLUE AT 2ND FLOOR CEILING
7) REMOVE CLIPS FROM FLEX GAS LINES
8) SHIM UPPER STRINGERS AT HEADER
9) SEAL TUB DRAIN HOLES
10) RE-INFORCE OVER BORED 2 X 4 STUD AT NORTH END OF GARAGE SHEARWALL AND BANG PLATE CONDENSATE IN SAME STUD
11) NO WATER PRESSURE (DWV OK)
12) STOPPED INSPECTION AFTER 1ST FLOOR