Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM02712
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2006 | FRAMING | Approved | IVRS - Inspection :* | |
12/29/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING MECH 2) 1" CLEARANCE TO B-VENT |
|
12/15/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADD HD FRONT NEAR DOOR WHERE MARKED 2) ADD RECEPTACLE WALL NORTH OF FRONT DOOR 3) PLUM MASTER IPC OR UPC 4) NO DWV TEST 5) NO VENT 6) REMOVE CLAMPS FROM FLEX GAS LINE 7) PRESSURE TEST OK 8) NEED 1" CLEAR TO B-VENT |
|
12/12/2005 | FRAMING | Denied | 1) ANCHOR BOLTS LOOSE THROUGHOUT/HOLDOWN SHEAR 2) BLOCKING MISSING AT COMBUSTION/FIREBLOCK GARAGE DROP 3) NO WATER DWV OR WATER PRESSURE PEX 4) SECURE 3" ? TO 2ND FLOOR/GARAGE FRESH AIR MISSING VENT BOX 5) FIRE BLOCK TUB ? AT DEN 6) TUB WALLS NOT INSULATED 7) NAIL PROTECT ELECTRIC WEST WALL SLIDER 8) STRAP GLU LAM TO STUDS AT KITCHEN WALL 9) RED HEAD AT ENTRANCE 8" FROM 1ST FLOOR 10) STOPPED INSPECTION |