Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM02708
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
08/31/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* HVC 412 REQD 1) NEED HANGOR SIZE BEAM REAR 2) NAIL SHEAR TRANSFER BOXES REAR PORCH 3) PUT BEARING UNDER INT. ROOF STRUCTURE, AT FURN AREA 4) VERIFY HANGOR AT BEAM TO BEAM LIV. ROOM 5) 3 PT. FLR. TRUSSES MISSED BEARING PTS 6) SHIM ALL 3 PT. BEARING? |
|
08/29/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MANY ROWS OF ROOF NAILING MISSED 2) SHEAR X-FER PANELS NOT NAILED THROUGH ROOF 3) N. SIDE DIAGONAL BRACING IS SHORT 4) SEVERAL ROWS OF SHEAR NAILING MISSED - PAINTED 5) NEED ALTERNATE H.D. AT FRONT ENTRY FOR BLOWOUT 6) ARCH HEADER AT BOTTOM OF STAIR CALLS FOR 2 - 2X6 TRIMMERS 7) STRAP CORNERS OF WEST LOWER GABLE TRUSS |