Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM02708

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
09/08/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/31/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
HVC 412 REQD
1) NEED HANGOR SIZE BEAM REAR
2) NAIL SHEAR TRANSFER BOXES REAR PORCH
3) PUT BEARING UNDER INT. ROOF STRUCTURE, AT FURN AREA
4) VERIFY HANGOR AT BEAM TO BEAM LIV. ROOM
5) 3 PT. FLR. TRUSSES MISSED BEARING PTS
6) SHIM ALL 3 PT. BEARING?
08/29/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MANY ROWS OF ROOF NAILING MISSED
2) SHEAR X-FER PANELS NOT NAILED THROUGH ROOF
3) N. SIDE DIAGONAL BRACING IS SHORT
4) SEVERAL ROWS OF SHEAR NAILING MISSED - PAINTED
5) NEED ALTERNATE H.D. AT FRONT ENTRY FOR BLOWOUT
6) ARCH HEADER AT BOTTOM OF STAIR CALLS FOR 2 - 2X6 TRIMMERS
7) STRAP CORNERS OF WEST LOWER GABLE TRUSS