Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2005 | PLUMBING - FINAL | Approved | ||
| 09/27/2005 | PLUMBING - FINAL | Not ready for Inspection | EACH WATER SUPPLIED DEVICE SHALL HAVE ITS OWN BACKFLOW PROTECTION-MAY NOT COMBINE DEVICES. INDIRECT WASTE PIPING MAYNOT BE COMBINED. INDIRECT WASTE PIPING SHALL BE APPROVED MATERIAL INSTALLED IN ACCORDANCE TO 94 UPC. ALL AIR GAPS TO BE A MINIMUN OF ONE INCH SPLASHING NOT PERMITTED. PROVIDE CERTS FOR BACKFLOW DEVICES PROVIDE DRAIN WHERE REQU'D | |
| 09/27/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE READ AND FOLLOW INSPECTION COMMENTS FROM PAST INSPECTIONS 2) USE APPROVED FITTINGS ON ALL PIPING 3) SUPPORT AND SECURE ALL PIPING AND DEVICES |
|
| 09/26/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE CORRECTIONS FROM 9/23/05 INSPECTION. TEMP C OF O FOR STOCKING ONLY. |
|
| 09/23/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/22/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |