Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/31/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WE HAVE BOX OVERFILL IN FRONT SOFFIT 314.16
2. BOND JUNCTION BOX FRONT.
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20
4. FULLY TERMINATE CONDUCTORS AT SCREW TERMINALS. IF STRANDED USE A TERMINAL END TO TERMINATE.
5. EM LIGHTING TO BE ON CIRCUIT SERVING AREA 700.12
6. PLEASE PROVIDE ACCESS TO ROOF FOR INSPECTION.