Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/31/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WE HAVE BOX OVERFILL IN FRONT SOFFIT 314.16 2. BOND JUNCTION BOX FRONT. 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 4. FULLY TERMINATE CONDUCTORS AT SCREW TERMINALS. IF STRANDED USE A TERMINAL END TO TERMINATE. 5. EM LIGHTING TO BE ON CIRCUIT SERVING AREA 700.12 6. PLEASE PROVIDE ACCESS TO ROOF FOR INSPECTION. |