Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2006 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 05/17/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 05/16/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. NEED SUPPORT WIRES ON BOXES IN CEILING. 2. MFG FIXTURE CLIPS TO BE EFFECTIVE. 3. NEED TO PROTECT CONDUCTORS AT NIPPLE. 4. PREVENT OBJECTIONABLE CURRENT ON GROUNDING CONDUCTOR 250.6 5. PLEASE IDENTIFY NEUTRAL CLOSER TO WEATHERHEAD. 6. A BOND WILL BE NEEDED FOR TEMP. POWER |