Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/17/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BOND METER ENCLOSURE NEC 250.92 2) WATER BOND TO SERVICE ENCLOSURE-NEC 250.104 (1) 3) USE PROPER SIZE BOND CONDUCTOR NEC 250.102 (C) 4) IDENTIFY SERVICE DISCONNECT NEC 230.70 (B) |
|
| 05/16/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |