Permit: T05CM02696

Parcel: 107110010


Addresses:

3175 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/02/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/17/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) BOND METER ENCLOSURE NEC 250.92
2) WATER BOND TO SERVICE ENCLOSURE-NEC 250.104 (1)
3) USE PROPER SIZE BOND CONDUCTOR NEC 250.102 (C)
4) IDENTIFY SERVICE DISCONNECT NEC 230.70 (B)
05/16/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*