Permit: T05CM02682

Parcel: 107111720


Addresses:

216 W BLACKLIDGE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/03/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/20/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/14/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) #1 OK
2) WORK IS INCOMPLETE
3) OPEN WIRING
4) UNPROTECTED WIRING
5) NO SMOKE DETECTORS
06/27/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) INSTALL 2 GROUND RODS MIN 6' APART, BOND WATER & GAS PIPING. 2) ALL CIRCUIT BREAKERS MUST BE OF SAME MANUF, AS PANEL. 3) NOTE THAT METER IS INSTALLED AND SERVICE IS ENERGIZED, METER COMP. SEALED. 4) LOOSE UNTERMINATED WIRING INSISDE PANEL COMP.MC CABLE NOT TERMINATED PROPERLY. VERIFY LICENSED CONTR. DOING WORK. NAME, PH#