Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM02678
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/25/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS. |
|
05/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FEEDERS FROM TRANSFORMER NEED PROTECTION FROM PHYSICAL DAMAGE UNLESS LISTED FOR USE. 2. IDENTIFY ALL BRANCH CKTS IN PANEL(S). 3. MAINTAIN RAINTIGHT INTERGRITY ON TRANSFORMER DISTRIBUTION PANEL & OPEN FOR INTERIOR INSPECTION. |