Permit: T05CM02678

Parcel: 11202034A


Addresses:

3838 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
07/01/2005 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
1) OK TO CLEAR (2) METERS
06/29/2005 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :* TRAILER: 1) CORRECTLY IDENTIFY CONDUCTORS AT WEATHER HEAD AND DISCONNECT 2) SUPPORT SEAL TITE AT POLE TO PREVENT PVC BREAKAGE.
SERVICE POLE: 1) CORRECTLY IDENTIFY CONDUCTORS AT WEATHER HEAD AT BREAKER LINE & LOAD. 2) BOND ENCLOSER-NEUTRAL DISCONNECT LINK-SCREW. 3) IDENTIY VOLTAGE AT SERVICE.