Inspection Status: Denied
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2006 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECT LEAK ON T&P DRAIN USE CORRECT DRAINAGE FITTING FOR VENTING BELOW FLOOD RIM T&P SHALL TERMINATE 6"-24" ABOVE GRADE INTER MEMBERING OF DISSIMILAR METALS IS PROHIBITED IN NEW CONSTRUCTION USE PROPER C/O PLUG TO ACCEPT C/O SCREW USED TO HOLD C/O COVER IN PLACE - DRILLING OR TAPPING ABS IS PROHIBITED |