Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T05CM02677
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2006 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECT LEAK ON T&P DRAIN USE CORRECT DRAINAGE FITTING FOR VENTING BELOW FLOOD RIM T&P SHALL TERMINATE 6"-24" ABOVE GRADE INTER MEMBERING OF DISSIMILAR METALS IS PROHIBITED IN NEW CONSTRUCTION USE PROPER C/O PLUG TO ACCEPT C/O SCREW USED TO HOLD C/O COVER IN PLACE - DRILLING OR TAPPING ABS IS PROHIBITED |