Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05CM02647
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
08/04/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
07/07/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* PLEASE SEE NOTES ABOVE AND SUPPLY SPEC'S FOR JOB WHAT WILL YOUR OXYGEN SYSTEM PRESSURE BE? | |
07/05/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) HAVE BUILDING NUMBER ADDED TOYOUR PERMIT. 2) PROVIDE TEST ON GAS PIPING SYSTEM. 3) SHALL USE APPROVED PIPING MATERIALS AND FITTINGS ON PROPANE GAS PIPING. 4) PROVIDE LISTING SHEET FOR REGULATORS USED ON PROPANE GAS PIPING SYSTEM. 5) EXISTING PROPANE BOTTLES HAVE ACETYLENE REGULATORS IN USE ON THEM. ADVISED RAY MCKEE THIS IS INCORRECT AND IS AN UNSAGE CONDITION. 6) PLEASE PROVIDE INFORMATION ON YOUR SYSTEM PROPANE OPERATING PRESSURE. 7) PLEASE SEE SECTION 94 UPC SECTION 1211.15 FOR VALVES AT APPLIANCE LOCATIONS. ALSO SEE 1213.7, 1213.8 AND 1218.5 |