Permit: T05CM02618

Parcel: 133369570

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM02618

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/13/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1) DISCONNECTING MEANS FOR WATER HEATER
2) TIGHTEN LOOSE FITTING
3) OK FINAL
09/07/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT M/C CABLE 12"
2) OK WALLS AND CEILING
3) BOXES MORE THAN 1/4" NEEDED EXTENDER RINGS 314.20
08/15/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) PROTECT M/C CABLE AT TOP PLATE 300.4
2) PRVENT DIELECTRIC CONTACT WITH COPPER PIPING
3) SUPPORT M/C CABLE 6' ON VERTICAL RUN
4) WHERE IS EXHAUST FAN ?
5) WHERE ARE ELECTRICAL PLANS?
6) PLEASE ADD 02035 TO PERMIT
7) EXISTING RECEPTACLE TO BE EXTENDED OUT