Permit: T05CM02611

Parcel: 127022350


Addresses:

5150 E SPEEDWAY BL


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM02611

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/19/2006 ELECTRIC - FINAL Approved OK FOR TEMP C/O SUBJECT TO OTHER INSPECTORS
01/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) INSTA HOT WATER HEATER TO HAVE DISCONNECTING MEANS
2) MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECTS
3) CLEAN SURFACES UNDER LUGS
4) LABEL DISCONNECTING MEANS
5) FINISH PANEL SCHEDULES
6) BOND JUNCTION BOX
7) SPLIT BOLTS ONLY LISTED FOR CONDUCTORS
8) VERIFY FUSE PROTECTION FOR MOTERS
9) FINISH ELECTRIC MAKE UP
10) FINISH SUPPORTING CONDUIT
11) INSTALL MISSING COVERS
12) OUT DOOR LIGHTING NOT PER PLANS
12/23/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK TRIM FRONT BUILDING INTERIOR