Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/19/2006 | ELECTRIC - FINAL | Approved | OK FOR TEMP C/O SUBJECT TO OTHER INSPECTORS | |
| 01/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INSTA HOT WATER HEATER TO HAVE DISCONNECTING MEANS 2) MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECTS 3) CLEAN SURFACES UNDER LUGS 4) LABEL DISCONNECTING MEANS 5) FINISH PANEL SCHEDULES 6) BOND JUNCTION BOX 7) SPLIT BOLTS ONLY LISTED FOR CONDUCTORS 8) VERIFY FUSE PROTECTION FOR MOTERS 9) FINISH ELECTRIC MAKE UP 10) FINISH SUPPORTING CONDUIT 11) INSTALL MISSING COVERS 12) OUT DOOR LIGHTING NOT PER PLANS |
|
| 12/23/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK TRIM FRONT BUILDING INTERIOR |