Permit: T05CM02608

Parcel: 116124810

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
08/22/2005 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
08/18/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FOOTINGS TO BEAR MINIMUM 12" BELOW NATURAL GRADE
2) PA STRAPS INCORRECTLY INSTALLED - MUST HAVE MORE DEPTH INTO CONCRETE AND CONCRETE BETWEEN STRAP AND FORM
3) MINIMUM 15" OVERLAP ALL REBAR
4) WRAP ALL PLB IN CONTACT WITH CONCRETE FOAM
5) MINIMUM 3" CLEARANCE REBAR TO DIRT AND FORMS
6) NO PLANS/PERMIT VISIBLE - CHECK SETBACKS AND FOOTINGS, ETC.
7) STOPPED INSPECTION