Permit: T05CM02599

Parcel: 110060760

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/17/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/16/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
USE LATEX PAINT NOT ENAMEL, SEAL ROOF JACK AT CONDENSATE - SECURE LINER IN DUCT, ALL UNITS
01/10/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PAINT EXPOSED PVC W/LATEX PAINT
- TIGHTEN LOOSE ELEC. CONNECTIONS
- SPLITTER NOT SEALED PROPERLY TO SEPARATE SUPPLY FROM RETURN
- DO NOT USE TAPE INSIDE DUCT
- REMOVE SCREWS FROM DRYER VENTS
- PROVIDE ANGLED PLUGS ON SOME KITCHEN EXHAUST FANS AS NEEDED
- PROVIDE R8 DUCT LINER IN EXPOSED DUCT
ON ROOF AS PER 1998 IECC SECTION 503.3.3