Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/16/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* USE LATEX PAINT NOT ENAMEL, SEAL ROOF JACK AT CONDENSATE - SECURE LINER IN DUCT, ALL UNITS |
|
| 01/10/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PAINT EXPOSED PVC W/LATEX PAINT - TIGHTEN LOOSE ELEC. CONNECTIONS - SPLITTER NOT SEALED PROPERLY TO SEPARATE SUPPLY FROM RETURN - DO NOT USE TAPE INSIDE DUCT - REMOVE SCREWS FROM DRYER VENTS - PROVIDE ANGLED PLUGS ON SOME KITCHEN EXHAUST FANS AS NEEDED - PROVIDE R8 DUCT LINER IN EXPOSED DUCT ON ROOF AS PER 1998 IECC SECTION 503.3.3 |