Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 05/16/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* UPC - PIPING INSTALLED IN A CONCRETE FOOTING SHALL BE SLEEVED OR INSTALLED IN RECESSED CHANNELS OR I'M ONLY ASKING FOR FOAM WRAP |
|
| 05/15/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* FOAM PIPE WRAP IS TO COVER ALL PIPING IN CONCRETE NOTE: CLOSET FLANGES ARE REQUIRED TO BE FASTENED TO FLOOR. |
|
| 05/12/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE VACUUM BREAKERS ON CONSTRUCTION HOSE BIBS. 2. HAVE ALL PIPES WRAPPED AT PENETRATION THRU CONCRETE. |
|
| 05/11/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" ABS BUILDING SEWER INSTALLED PER STAMPED PLAN. CONNECTED TO EXISTING CLAY HCS. OK TO COVER. 2" SCH 40 PVC WATER LINE OK 2" SCH 40 PVC LANDSCAPING WATER PIPING INSTALLED. NEW WATER METERS NOT YET INSTALLED. CONNECTED TO 5/8" M. PROVIDE CONTINUOUS SUPPORT UNDER PIPING INSTALL VAC BREAKERS. |
|
| 05/08/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* FROM BUILDINGS INTERIOR UNDERGROUND WATER TEST THRU 2-WAY CLEANOUTS TO 4" BUILDING SEWER APP. 40' FROM ROAD. 1. NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE. 2. HAVE APPROVAL STAMP ON SITE PLAN FOR SEWER. 03040-WATER PIPING TO BE INSTALLED PER PLAN OR PROVIDE REVISED APPROVED PLAN. SITE PLAN TO HAVE PLAN CHECK APPROVAL STAMP. |