Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/22/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 01/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH PREVIOUS ITEMS 1, 2, 3, 4, 5, 7, 8 AND 9 |
|
| 01/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* CALLED JESSIE NO ANSWER LOCKED |
|
| 01/09/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PANEL DIRECTORIES TO BE AS PER 408.4 LEGIBLE, NO GENERIC LABELING, NO ABBREVIATIONS 2. OUTDOOR RECEPTACLES COVERS TO BE AS PER 406.8 3. FULLY INSTALL CONDUCTORS UNDER RECEPTACLE TERMINAL SCREWS 4. USE APPROVED EXTENDER RING FOR BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES AND FLUSH IN COMBUSTIBLES 314.20 - DEVICE & LIGHTS 5. BOXES MORE THAN 1/8" AROUND BOX - 314.21 6. MISSING PLATES 7. TIGHTEN LOOSE FITTINGS A/C UNITS 8. SECURE CABLE TO ENCLOSURE 312.5 9. RACEWAY TO BE CONTINUOUS T-STAT WIRE 10. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER #1101 ONLY FINISH OTHER UNITS |