Permit: T05CM02599

Parcel: 110060760

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/22/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled
01/16/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH PREVIOUS ITEMS 1, 2, 3, 4, 5, 7, 8 AND 9
01/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CALLED JESSIE NO ANSWER
LOCKED
01/09/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PANEL DIRECTORIES TO BE AS PER 408.4
LEGIBLE, NO GENERIC LABELING, NO ABBREVIATIONS
2. OUTDOOR RECEPTACLES COVERS TO BE AS PER 406.8
3. FULLY INSTALL CONDUCTORS UNDER RECEPTACLE TERMINAL SCREWS
4. USE APPROVED EXTENDER RING FOR BOXES MORE
THAN 1/4" IN NON-COMBUSTIBLES AND FLUSH IN COMBUSTIBLES 314.20 - DEVICE & LIGHTS
5. BOXES MORE THAN 1/8" AROUND BOX - 314.21
6. MISSING PLATES
7. TIGHTEN LOOSE FITTINGS A/C UNITS
8. SECURE CABLE TO ENCLOSURE 312.5
9. RACEWAY TO BE CONTINUOUS T-STAT WIRE
10. A DISCONNECTING MEANS IS NEEDED FOR
WATER HEATER #1101 ONLY FINISH OTHER UNITS