Permit: T05CM02599

Parcel: 110060760

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1) CORRECTLY IDENTIFY GROUNDING ELECTRODE CONDUCTOR
09/27/2007 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*
1) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED CONDUCTOR
2) BOND JUMPER TO BE SIZED PER 250.102 AND 250.66
3) MAINTAIN WORKING CLEARANCES
4) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
5) CLEAN EXCESS DIRT FROM BOTTOM OF PANELS
09/25/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
THIS IS FOR TEMP POWER FOR TEST - NO RECORD OF INTERMEDIATE INSPECTION - PLEASE VERIFY - ALSO, HAVE ELECTRICIAN PRESENT TO OPEN PANELS & SERVICE EQUIPMENT
02/21/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*