Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 10/04/2007 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) CORRECTLY IDENTIFY GROUNDING ELECTRODE CONDUCTOR |
|
| 09/27/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* 1) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED CONDUCTOR 2) BOND JUMPER TO BE SIZED PER 250.102 AND 250.66 3) MAINTAIN WORKING CLEARANCES 4) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT 5) CLEAN EXCESS DIRT FROM BOTTOM OF PANELS |
|
| 09/25/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THIS IS FOR TEMP POWER FOR TEST - NO RECORD OF INTERMEDIATE INSPECTION - PLEASE VERIFY - ALSO, HAVE ELECTRICIAN PRESENT TO OPEN PANELS & SERVICE EQUIPMENT |
|
| 02/21/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |