Permit: T05CM02599

Parcel: 110060760

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/22/2006 ELECTRIC - INTERMEDIATE Approved CONTRACTOR TO CALL BACK WHEN SERVICE ARRIVES AND IS INSTALLED AND PNL FEEDERS TAKEN OUT AND PUT IN ENCLOSURES.
11/20/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
THE SIDE PANEL SUPPORT IN UNIT 1102 WAS REMOVED.
REINSTALL ON NORTH SIDE OF PANEL -- WILL CHECK ON FINAL.
11/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE TO GENERAL CONTRACTOR, THE ELECTRICAL CONTRACTOR HAS FINISHED HIS CORRECTIONS, HOWEVER, INTERMEDIATE WILL NOT BE APPROVED UNTIL FRAMERS HAVE REPAIRED DAMAGED 2X4 WOOD ABOVE ELECTRICAL PANELS AT CEILING HIGH. RECALL WHEN COMPLETE ALL WILL RELEASE EXCEPT SOUTH WALL THEN ONLY WHEN FEEDERS TO PANELS TAKEN OUT.
11/08/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1107
1. UNIT 1107 - REPAIR BROKEN WOOD (2X4) WHICH WIRING COMES DOWN INTO PANEL, NEED TO SUPPORT WITHIN 12" OF PANEL - ALL WIRING.
2. REPAIR 2X4 AT TOP OF 3GANG SW BOX AT EAST ENTRY BOTTOM FLOOR.
3. TAPE ORANGE ROMEX GOING THRU SHARP EDGE ON FLEX TO WATER HEATER.
4. QUESTION SHOULD AC FEED BE #4 -- OTHERS ARE.

1106
1. REPAIR WOOD TOP OF PANEL WHRE CIRCUITS COME DOWN FROM CEILING.
2. SLOPE WIRING ABOVE PNL WITHIN 12" OF PNL
3. TAPE #10 ROMEX TO FLEX AT WH
4. BOX NEEDED AT EAST PORCH FOR OUTSIDE LIGHT.
5. AT HALLWAY STRAP ALL WIRING SO IT DOES NOT GO BELOW CEILING.

1105
1. SAME AS 1106

1104
1. REPAIR WOOD AT WIRING ABOVE PNL
REMOVE UNNEEDED NAILS.
2. TAPE ROMEX AT FLEX FOR WH
3. 2ND FLOOR BR SW BOX - TOO MUCH ROMEX COVERING INSIDE BOX - TRIM.

1103
1. STRAP WIRING ABOVE PNL, TAPE ROMEX AT WH

1102
1. STRAP WIRING WITHIN 12" OF PNL, TAPE ROMEX TO FLEX AT WH.

1101
1. SOUTH WALL NOT COMPLETE - FEEDERS NOT THRU WALL YET PROTECT 1ST FLOOR BATHROOM SW LEGS AT CEILING.
11/07/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*