Permit: T05CM02573

Parcel: 11611003H

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/26/2012 PLUMBING - INTERMEDIATE Approved
12/23/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/08/2011 PLUMBING - INTERMEDIATE Partial Approval 1) NEED TO SEE CLOSET FLANGES
2) PVC AND PEX OK
12/05/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PLEASE CALL IN PRIVATE SEWER PERMIT SO I CAN DOCUMENT MANHOLE #9 TEST. FAILURE TO DO SO, COULD CAUSE YOU DELAYS WHEN TRYING TO OBTAIN C OF O
2) TRAILER LOCKED, FIELD PLAN DOES NOT INCLUDE DELTA 3 REVISION
3) CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE
09/26/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NO TEST ON WATER SERVICE STUB IN. THERE WAS NO TEST ON 9/22/11 EITHER. ALSO THE END OF THE SERVICE PIPE HAS BEEN LEFT OPEN
2) TRAILER LOCKED, WITHOUT ACCESS TO PLANS AND PERMIT, I AM UNABLE TO MAKE INSPECTION. ALSO THE PLAN YOU HAD FOR 9/22/11 WAS DELTA 3 REVISION ONLY. HOW AM I SUPPOSED TO DO INSPECTION ?
3) YOU HAVE PERMISSION TO POOUR PAD #7 SUBJECT TO APPROVED PLAN. THIS IS A ONE TIME DEAL ONLY, YOU MUST BE PREPARED FOR INSPECTIONS
09/22/2011 PLUMBING - INTERMEDIATE Denied 1) HAVE PLUMBING CONTRACTOR READ 15410-3 3.02A-INSTALLER CERTIFICATION AND COMPLY
2) CAP OFF ALL OPEN PIPING PEX
3) PROVIDE AN APPROVED PLAN FOR BLDG #7-TYPE "B", WHAT YOU GAVE ME IS DETAL 3 REVISION ONLY
4) ALL PEX PIPING TO HAVE THE LISTING CONTINOUS ON THE PIPE. ANY SECTION WITHOUT CONTINOUS LISTING IS NOT ACCEPTABLE. MISSING LISTING INDICATES DAMGED PIPE