Permit: T05CM02563

Parcel: 110121000

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/20/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/13/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*OK TO CLEAR TO MAIN LOGS IN PANELS. CONTRACTOR TO MAINTAIN AND VERIFY LOCK OUT TAG OUT ORE CODERS
01/12/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) MULTIPLE TERMINATIONS AT LUG
2) BOND DISCONNECT ENCLOSURE ALSO PANEL ?
3) A BONDING DEVICE IS NEEDED INSIDE GUTTER AT NIPPLE
4) FINISH #4 PREVIOUS INSPECTION
5) INSTALL SERVICE CONDUCTORS
01/10/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. IDENTIFY GROUNDING EQUIPMENT CONDUCTOR
2. LUG TO BE SIZED FOR CONDUCTOR
3. NEED FUSES AND REJECTION PINS INSTALLED
4. FOR TEMP POWER FOR TESTING INSTALL ALL DEVICES 8' AND BELOW MAKE UP PANELS