Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/13/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*OK TO CLEAR TO MAIN LOGS IN PANELS. CONTRACTOR TO MAINTAIN AND VERIFY LOCK OUT TAG OUT ORE CODERS | |
| 01/12/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) MULTIPLE TERMINATIONS AT LUG 2) BOND DISCONNECT ENCLOSURE ALSO PANEL ? 3) A BONDING DEVICE IS NEEDED INSIDE GUTTER AT NIPPLE 4) FINISH #4 PREVIOUS INSPECTION 5) INSTALL SERVICE CONDUCTORS |
|
| 01/10/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. IDENTIFY GROUNDING EQUIPMENT CONDUCTOR 2. LUG TO BE SIZED FOR CONDUCTOR 3. NEED FUSES AND REJECTION PINS INSTALLED 4. FOR TEMP POWER FOR TESTING INSTALL ALL DEVICES 8' AND BELOW MAKE UP PANELS |