Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1. FINISH GRID 2. FINISH SUPPORTING UPU CABLING UP OFF OF PIPES OK TO TILE EXCEPT AS NOTED |
|
| 01/18/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/17/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) M/C TUBE SUPPORTED WITHIN 12" OF BOX FITTINGS 2) FINISH GRID TO INSTALL CANS TO GRID 3) MAINTAIN 517.13 WIRING METHODS FOR ENTIRE BRANCH CIRCUIT |