Permit: T05CM02542

Parcel: 11307085B


Addresses:

3067 N CAMPBELL AV

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
11/08/2005 MECHANICAL - INTERMEDIATE Approved PER MECH FINAL
08/14/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TEMP C OF O OK
2) PROVIDE WORKING PLATFORM TO COVER SUPPLY DUCTWORK FOR ACCESSING COMPRESSOR/CHANGE/REPLACE IN FUTURE
3) UNIT IMPROPERLY FUSED ? DATA PLATE NOT MARKED, DOES UNIT HAVE AUX. HEAT STRIP ? YES ? NO ?