Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM02538
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*OK FOR FINAL C OF O | |
11/23/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*AC-1 OVERFUSED 35 AMP MAX. NEED TO TEST DUCT SMOKE DETECTORS OK FOR TEMP C OF O TYPE I EXHAUST FANS MUST TERMINATE 10' FEET AWAY FROM WALLS OR AT TOP OF WALLS. SEE SECTION 506. 3.13.3 2000 IMC |