Permit: T05CM02538

Parcel: 136261280

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM02538

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/28/2005 PLUMBING - FINAL Approved IVRS - Inspection :*BUILDING INSPECTOR TO RECEIVE (1) BACKFLOW CERTIFICATION FOR CARBONATOR. RECEIVED (1) CARBONATOR + (3) DOUBLE CHECK ASSEMBLY BACKFLOW CERTIFICATIONS.
11/25/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
11/23/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*COMPLETE WORK, PROVIDE CORRECT BACKFLOW PROTECTION FOR ALL APPLIANCES WITH DIRECT WATER CONNECTION THTAT REQUIRE PROTECTION
11/21/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* ICE MACHINE DRAIN TO BE SEPARATE.
ALL GAS APPLIANCES TO BE INSTALLED & HOOKED UP WITH CORRECT GAS FLEX
DRAINS AT SODA DISPENSING EQUIPMENT TO BE SEPARATE
WEST ICE MACHINE DRAIN TO BE SECURED & TERMINATED PROPERLY
DRAIN FROM SODA DISPENSER TO BE RIDGID PIPING SUPPORTED CORRECTLY GRAVITY DRAIN TO RECEPTOR.
TRAP PRIMER VALVES TO BE TURNED ON.
(2) CARBONATORS REQUIRE (2) REDUCED PRESSURE BACKFLOW DEVICES ( 1) FOUR EACH UNIT. TESTABLE BACKFLOW PROTECTION IS ALSO REQUIRED FOR WATER SUPPLY TO NON CARBONATED BEVERAGES (1) FOR EACH PIECE OF EQUIPMENT.