Permit: T05CM02534


Addresses:

8248 S HOUGHTON RD


Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T05CM02534

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2006 SITE - SEWER Approved IVRS - Inspection :*
RECEIVED DISCHARGE AUTHORIZATION FROM PDEQ 5/1/06
05/19/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
04/14/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
VACUUM TEST MANHOLE #1 OK
VACUUM TEST MANHOLE #2 OK
6" SEWER FROM MANHOLE #2 TO SOUTHEND OF BUILDING
4 PSI AIR TEST OK
04/07/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
04/05/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
AIR TEST FROM MANHOLE #1 TO MANHOLE #2 INCLUDING NORTH HCS LATERAL OK
04/03/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM MANHOLE #1 TO MANHOLE #2 INCLUDING (2)
6" HCS LATERALS OK PENDING NOTES FROM 3/28/06 INSPECTION.
03/31/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
CONTINUATION OF 8" SDR 35 SEWER TO MANHOLE #2
6" SDR 35 OUT OF MANHOLE #2 SOUTHEAST FOR HCS BEDDING, SHADING, LAYING OK
03/30/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
CONTINUATION OF 8" SDR INCLUDING 6" BRANCH TO NORTHWEST END OF BUILDING APP. 50' NORTH OF
MANHOLE# 2. BEDDING, SHADING, LAYING OK
03/29/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR 35 BEDDING, SHADING & LAYING CONTINUOUS SOUTH APP. ANOTHER 80'
03/28/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR 35 FROM AREA OF NEW MANHOLE #1 SOUTH APP.
100' - 1. WILL NEED AIR TEST ON PIPING, VACUUM TEST ON MANHOLES, VERIFICATION OF GRADE AND AUTHORIZATION TO DISCHARGE AT LATER DATE.
03/14/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE APPROVED PLAN FOR SITE SEWER.