Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T05CM02534
Inspection Description - SITE - SEWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2006 | SITE - SEWER | Approved | IVRS - Inspection :* RECEIVED DISCHARGE AUTHORIZATION FROM PDEQ 5/1/06 |
|
05/19/2006 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
04/14/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* VACUUM TEST MANHOLE #1 OK VACUUM TEST MANHOLE #2 OK 6" SEWER FROM MANHOLE #2 TO SOUTHEND OF BUILDING 4 PSI AIR TEST OK |
|
04/07/2006 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
04/05/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* AIR TEST FROM MANHOLE #1 TO MANHOLE #2 INCLUDING NORTH HCS LATERAL OK |
|
04/03/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM MANHOLE #1 TO MANHOLE #2 INCLUDING (2) 6" HCS LATERALS OK PENDING NOTES FROM 3/28/06 INSPECTION. |
|
03/31/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* CONTINUATION OF 8" SDR 35 SEWER TO MANHOLE #2 6" SDR 35 OUT OF MANHOLE #2 SOUTHEAST FOR HCS BEDDING, SHADING, LAYING OK |
|
03/30/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* CONTINUATION OF 8" SDR INCLUDING 6" BRANCH TO NORTHWEST END OF BUILDING APP. 50' NORTH OF MANHOLE# 2. BEDDING, SHADING, LAYING OK |
|
03/29/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 8" SDR 35 BEDDING, SHADING & LAYING CONTINUOUS SOUTH APP. ANOTHER 80' |
|
03/28/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 8" SDR 35 FROM AREA OF NEW MANHOLE #1 SOUTH APP. 100' - 1. WILL NEED AIR TEST ON PIPING, VACUUM TEST ON MANHOLES, VERIFICATION OF GRADE AND AUTHORIZATION TO DISCHARGE AT LATER DATE. |
|
03/14/2006 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* 1. SHALL PROVIDE APPROVED PLAN FOR SITE SEWER. |