Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM02522
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE. OK FOR FINAL C OF O | |
10/18/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 50 AMP FUSES TO LARGE-45 AMP IS MAX 2) PROVIDE A SUN SHIELD OVER CANVAS CONNECTORS 3) PROVIDE A ROOF JACK AT CONDENSATE PENETRATION 4) PROVIDE A T-TOP FOR DRYER VENT 5) RECONNECT EXHAUST DUCT ABOVE CEILING 6) NEED TO TEST DUCT SMOKE DETECTOR |