Permit: T05CM02522

Parcel: 13323190A


Addresses:

7784 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM02522

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2005 ELECTRIC - INTERMEDIATE Approved
10/04/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK FRAME WALLS EXCEPT BATHROOMS
10/03/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*PROTECT CABLE & FLEX AT CROSS BRACES
SUPPORT M/C CABLE WITHIN 12" OF BOX NOT OFF OF CONDUITS
SUPPORT CONDUIT WITHIN 3' OF PVC FITTING AND AT TOP
SUPPORT M/C CABLE WITHING 12" OF PANEL
FINISH BATHROOM.
10/02/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/29/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* SUPPORT AND PROTECT M/C CABLE IN CHANEL AND AT TOP PLATES PROPERLY SUPPORT M/C CABLE
PREVENT DIE ELECTRIC CONTACT
UNCOVER BATH FIXTURE BOX. FILL UNUSED OPENING IN FIXTURE
PLANS CALL FOR CONDUIT. PLEASE PROVIDE A LETTER AUTHORIZING USE OF FLEX AND M/C CABLE
WHERE IS BATH EXHAUST FAN?
UNDERGROUND INSTALLED WITHOUT INSPECTION. UNCOVER IF TO BE USED.
WALLS COVERED WITHOUT INSPECTION. PLEASE UNCOVER TO INSPECT.
NOTE. VDV CABLEING TO BE AS PER 725.2 & 6, 800.2 2 & 6