Permit: T05CM02517

Parcel: 141015630

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM02517

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/10/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PROPERTY PINS EXPOSED
2) YOU HAVE 12 FIXTURE UNITS ON A 2" DRAIN LAUNDRY 2, 2 SHOWERS 4, 2 LAVS 4, 1 KITCHEN SINK 2 = 12 UNITS-MAXIMUM 8
3) REAR WATER CLOSET IS ON THE WRONG SIDE OF THE WALL