Permit: T05CM02515

Parcel: 128100550


Addresses:

250 S WILLIAMS BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/28/2006 MECHANICAL - INTERMEDIATE Approved
06/29/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSULATE 2' SECTION OF REFER LINE 4TH FLOOR SHAFT PRIOR TO SHEETROCK
06/26/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED REFER LINES IN SHAFT
2) OK TO PROCEED WITH INSULATION
3) SECURE AS NEEDED
4) RECALL FOR INSPECTION
06/15/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED CONDENSOR WATER PIPING ALL FLOORS.
04/06/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/13/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER LINE SETS FOR STAIRWELL UNITS
2) WORK PROGRESSING
3) DISCUSSED GREASE DUCTS
02/27/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLR FIRE DAMPERS - CAFETERIA WRAPPED OPENINGS.
JOB PROGRESSING
SUSPENDED MTL. LINED RET. AIR BOOTS - STRAPPED SUSPENDED
01/13/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*SUSPENDED ROUGH DUCT. OK TO INSULATE ALL. PROVIDE LEAK TES REPORT