Permit: T05CM02515

Parcel: 128100550


Addresses:

250 S WILLIAMS BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM02515

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED (1) COPY BACTERIA REPORT OK
PROVIDE ANSUL VALVE SIGN LOCATION.
08/17/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
RECEIVED (4) MAIN & (5) IN-HOUSE BACKFLOW CERTIFICATIONS
1. NEED TO SEE COMPLETION OF HOT TABLES IN KITCHEN AREA.
NO PROBLEMS FOR TEMP C OF O
AND COPY OF FINAL WATER BACTERIA REPORT PRELIMINARY RESULTS ARE CLEAN.
08/16/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
2ND, 3RD, 4TH FLOORS FIXTURES OK FOR FINAL.
1ST FLOOR FIXTURES, EXCEPT KITCHEN AREA OK
2ND, 3RD, 4TH FLOOR ICE MACHINE SHALL BE INSTALLED
SEE NOTES FROM 8/15/06
08/15/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. COMPLETE INSTALL OF ALL FIXTURES, MAKE WATER PROOF, INSTALL CLEANOUT, SECURE EXPANSION TANKS.
2. PROVIDE BACTERIA REPORT
3. PROVIDE BACKFLOW CERTIFICATIONS FOR IN HOUSE DEVICES.
4. FLOOR SINKS TO BE FLUSH IN BREAKROOMS.
5. KITCHEN EQUIPMENT TO BE INSTALLED.