Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM02515
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK U.G ALONG WEST END BALLARD LIGHTING |
|
07/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SOFFIT LIGHTING, TRANS BOTTOM SOUTH & EAST FOYER WALLS (WEST FOYER) |
|
06/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PARTIAL WEST OFFICES 3RD FLOOR 2) OK NORTH STAIRWELL |
|
06/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SOUTH STAIRWELL ROOF EQUIP. LAYOUT |
|
06/15/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 4TH FLOOR SOUTH OFFICES, RESTROOM 4TH NORTH OFFICES ELEC. ROOM PANELS OK U.P.S TERM (PROVIDE LETTER ON TORQ OF UPS TERM) UPS COMP. ROOM |
|
06/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLOOR CONF. ROOM |
|
06/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLOOR LIGHTING KITCHEN @ 3RD FLOOR |
|
06/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CORRIDOR CAN LTS. 2ND & 3RD FLOOR |
|
06/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK WEST OFFICES 4TH FLOOR - OK SOFFITS NORTH & ELEVATOR AREA |
|
06/02/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EAST OFFICES & WEST SOFFIT LTG. OK |
|
05/24/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 4000 AMP SWITCH GEAR GFI TEST PERFORMED ACCORDING TO MANUFACTURER TEST INSTRUCTIONS. 1ST & 2ND FLOOR BATHROOMS, CAN LIGHTS 2ND FLOOR AND KITCHEN |
|
05/19/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLOOR AS DISCUSSED |
|
05/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SOUTH STAIRWELL CORRIDOR & F.A 3RD FLOOR CORE |
|
05/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/05/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SEAT WALL, HARD LIDS CAFETERIA CAN LTS, 2 POLE BASES EAST ENTRY BY JOB TRAILER. |
|
04/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CALL DAN 1/2 HR. PRIOR TO INSP. AT 977-0287 DUCT WORK NEEDS TO MOVE WHERE LESS THAN 6' ABOVE U.P.S - GEAR PER ART. 110-26 2002 N.E.C |
|
04/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD FLOOR EAST OFFICES |
|
04/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR OFFICES WEST CONF. RM. LARGE & SMALL OK OFFICES (2) NORTH OF ELEVATOR. |
|
04/04/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WALLS 1ST & 2ND FLOOR AS DISCUSSED W/JAY |
|
03/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLOOR ELEVATOR SHAFT NORTH |
|
02/22/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*OPEN KO'S PLASTER RINGS NEEDED TIGHTEN ALL SUPPORT |
|
02/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK UPS ROOM 2) NOTE: ELECTRIC ROOM DOORS TO COMPLY WITH NEC 110-26 C (2) |
|
01/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |