Permit: T05CM02515

Parcel: 128100550


Addresses:

250 S WILLIAMS BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/18/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK U.G ALONG WEST END BALLARD LIGHTING
07/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SOFFIT LIGHTING, TRANS BOTTOM
SOUTH & EAST FOYER WALLS (WEST FOYER)
06/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PARTIAL WEST OFFICES 3RD FLOOR
2) OK NORTH STAIRWELL
06/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SOUTH STAIRWELL ROOF EQUIP. LAYOUT
06/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
4TH FLOOR SOUTH OFFICES, RESTROOM 4TH NORTH OFFICES
ELEC. ROOM PANELS
OK U.P.S TERM (PROVIDE LETTER ON TORQ OF UPS TERM)
UPS COMP. ROOM
06/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLOOR CONF. ROOM
06/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLOOR LIGHTING
KITCHEN @ 3RD FLOOR
06/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORRIDOR CAN LTS. 2ND & 3RD FLOOR
06/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK WEST OFFICES 4TH FLOOR
- OK SOFFITS NORTH & ELEVATOR AREA
06/02/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK EAST OFFICES & WEST SOFFIT LTG. OK
05/24/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
4000 AMP SWITCH GEAR GFI TEST PERFORMED ACCORDING TO MANUFACTURER TEST INSTRUCTIONS.
1ST & 2ND FLOOR BATHROOMS, CAN LIGHTS 2ND FLOOR
AND KITCHEN
05/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR AS DISCUSSED
05/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SOUTH STAIRWELL CORRIDOR & F.A 3RD FLOOR CORE
05/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/05/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SEAT WALL, HARD LIDS CAFETERIA CAN LTS, 2 POLE BASES EAST ENTRY BY JOB TRAILER.
04/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CALL DAN 1/2 HR. PRIOR TO INSP. AT 977-0287
DUCT WORK NEEDS TO MOVE WHERE LESS THAN 6' ABOVE U.P.S - GEAR PER ART. 110-26 2002 N.E.C
04/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR EAST OFFICES
04/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/12/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND FLOOR OFFICES WEST CONF. RM. LARGE & SMALL OK OFFICES (2) NORTH OF ELEVATOR.
04/04/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
WALLS 1ST & 2ND FLOOR AS DISCUSSED W/JAY
03/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR ELEVATOR SHAFT NORTH
02/22/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*OPEN KO'S PLASTER RINGS NEEDED
TIGHTEN ALL SUPPORT
02/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK UPS ROOM
2) NOTE: ELECTRIC ROOM DOORS TO COMPLY WITH NEC 110-26 C (2)
01/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*