Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM02514
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/25/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 03005 APPROVED BY R. MYERS ON 6/20/05 2) PLAN CALLS FOR HOT SIDE TO BE INSULATED. INSTALL PER PLAN OR PROVIDE ALTERNATE METHOD FOR E.C.C. COMPLIANCE (STAMPED LETTER FROM ARCHITECT) 3) OK TO COVER WALLS PENDING ARCHITECTS CHOICE OF COMPLIANCE |
|
07/22/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES FROM INSPECTION ON 7/20/05 2) PROVIDE SEPERATION ON HOT AND COLD TUBING 3) TUBING NEEDS TO BE INSIDE WALL SPACE |
|
07/20/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) POST AN ADDRESS PLEASE 2) PLEASE PROVIDE PROOF FO 03005 ROUGH SOIL INSPECTION 3) FINISH INTERMEDIATE PLUMBING WORK AND PROVIDE TEST ON SYSTEMS, THEN CALL FOR INSPECTION |