Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T05CM02514
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) OK TO CLEAR WHEN BOND POSTED AND INTERIOR IS TRIMMED 2) RESCHEDULE FUEL AND TEST POWER AT THIS TIME |
|
07/20/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL SERVICE PER T.E.P. 2) INSTALL RIGID NIPPLE ETC. ABOVE GRADE 3) PULL WIRE TO SERVICE, DISCONNECT AND PANEL |
|
07/19/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/12/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* IT LOOKS LIKE THERE IS 2" E.M.T GOING INTO THE GROUND? ( THIS IS NOT LEGAL) AGAIN! ELECTRICAL CONTRACTOR & GENERAL ARE NOT ON SITE. |
|
07/11/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
06/20/2005 | ELECTRIC - SERVICE UPGRADE | Denied | SERVICE REQUIRES 36" IN FRONT OF AND DOWN TO GRADE CLEARANCE TRANSFORMER PINS AND GAS METER BELOW SERVICE IN WAY. |