Permit: T05CM02511

Parcel: 11615194B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
*NOTE*
INSTALL ALL EQUIPMENT COVERS - NOW!
ADD EXTRA STRAP FOR EACH SECTION OF EMT ON ROOF FOR HOUSE LIGHTING RACEWAY.
03/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
#98 - OPEN GROUND DINING RECEPT, PANEL NOT CORRECTLY MARKED, REMOVE UNUSED CONNECTOR IN AC DISCONNECT.
#111 - NEED AC SERVICE OUTLET, OPEN GROUND ON DINING RECEPT. PANEL NOT CORRECTLY MARKED.
#108 - INSTALL COVERS ON DEVICES, PROVIDE CORRECTLY MARKED PANEL COVER.
#107 - INSTALL DEVICE COVERS
#104 - NOT READY
103, OPEN BULB IN CLOSET, LAUNDRY LIGHT NOT WORKING OUTLETS TO THE RIGHT OF KITCHEN SINK NOT WIRED CORRECTLY MAKE SURE PANEL IS CORRECTLY MARKED
100 - FRONT BEDROOM OUTLETS NOT WORKING
ALSO,
1. ALL UNITS NEED SERVICE OUTLETS FOR ROOF EQUIP.
2. ALL UNITS NEED TWO 20 AMP APPLIANCE CKT'S WITH NOTHING ELSE ON THEM - INCLUDIG DISHWASHER & DISPOSAL
DISH & DISP NEED SEPARATE CKT.
3. ALL WIRING FOR HOUSE LIGHTS NEED TO BE PROPERLY SECURED SUPPORTED AND WEATHERPROOF
4. YOU WILL NEED TO PAY A RE-INSPECTION FEE PRIOR TO FINISH APPROVAL.
03/16/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GO THROUGH ALL UNITS TO MAKE SURE THEY ARE READY FOR INSPECTION.
PANEL DIRECTORIES PROPERLY MARKED,
2 WIRE OUTLETS AS NEEDED
K.O. SEALS AS NEEDED,
2 SMALL APPLIANCE CKTS
03/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO OUTSIDE GFI OUTLETS
2. USE LISTED 2 WIRE NON GROUNDING RECEPTS ON UNGROUNDED CIRCUITS
01/25/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH UNITS
2) PROVIDE ROOF ACCESS
3) INSTALL UNIT NUMBERS
4) CALL FOR FINAL WHEN COMPLETE
5) WASHER CKT TO BE DEDICATED ? NEC 210.11