Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T05CM02511
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
03/01/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* SEE WRITE UP T05CM00887 |
|
02/16/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PROVIDE CORRECT FEEDER/UNIT LOAD CALCULATIONS |
|
02/10/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND GAS AND WATER TO SERVICE 2. SEPARATE NEUTRALS FROM GROUNDS IN SUB-PANELS 3. DO NOT INSTALL GROUND AND NEUTRAL UNDER SAME TERMINATION 4. DO NOT INSTALL DIFFERENT SIZE CONDUCTORS UNDER SAME TERMINATION. 5. SEAL UNUSED OPENINGS AND REMOVE UNUSED WIRING 6. NEED MINIMUM 60 AMP SERVICES 7. MAX 50 AMP ON #6 NMB |
|
02/01/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* GEORGE HUBBARD 272-3902 CUSTOM ELECT. SOLUTIONS |
|
01/30/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*SERVICE NOT READY |