Inspection History: SHEET ROCK NAILING

Permit Number - T05CM02495

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2005 SHEET ROCK NAILING Approved
07/08/2005 SHEET ROCK NAILING Partial Approval IVRS - Inspection :* PLEASE CLARIFY PLAN. CODE ANALYSIS CLAIMS NON SEPARATED USE BUT THEN STATES 1 HR SEPARATION IS AN APPLICABLE CONDITION. WHICH IS IT? PLAN DETAILS SHOW 1 HR WALL ON EAST SIDE. THIS WILL REQUIRE FIRE STOP SYSTEM FOR JOINTS AND PENETRATIONS; EXTENSION OF WALL TO OUTSIDE OF OUTSIDE WALL OR DELETION FROM PLAN.