Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
Permit Number - T05CM02488
Inspection Description - SHEET ROCK NAILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2005 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
| 06/23/2005 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTES FOR EXISTING FULL HEIGHT WALL AT SOUTH SIDE ARE IN CORRECT. WALL IS NOT FULL HEIGHT. 2) UL SYSTEM U 1525 IS OF USE WITH CONCRETE MASONRY SPACED 24 " O.C. PLEASE PROVIDE A USABLE UL SYTEM FOR YOUR 2 HOUR BARRIER. 3) TALK TO YOUR ARCHITECT TO REVISE PLANS FOR EXISITING CONDITIONS AND TO PROVIDE CORRECT U.C SYSTEM FOR FIRE BARRIERS. 4) PROVIDE LISTED FIRESTOP SYSTEM FOR PENETRATIONS. |