Permit: T05CM02488

Parcel: 13510150R

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Permit Number - T05CM02488

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/07/2005 SHEET ROCK NAILING Approved IVRS - Inspection :*
06/23/2005 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NOTES FOR EXISTING FULL HEIGHT WALL AT SOUTH SIDE ARE IN CORRECT. WALL IS NOT FULL HEIGHT. 2) UL SYSTEM U 1525 IS OF USE WITH CONCRETE MASONRY SPACED 24 " O.C. PLEASE PROVIDE A USABLE UL SYTEM FOR YOUR 2 HOUR BARRIER. 3) TALK TO YOUR ARCHITECT TO REVISE PLANS FOR EXISITING CONDITIONS AND TO PROVIDE CORRECT U.C SYSTEM FOR FIRE BARRIERS. 4) PROVIDE LISTED FIRESTOP SYSTEM FOR PENETRATIONS.