Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM02455
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/28/2005 | FRAMING | Approved | IVRS - Inspection :* | |
09/27/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN ANCHOR BOLTS 2) SUPPORT VENT 90 TO ROOF IN LAUNDRY 3) SHIM HEADERS WHERE NEEDED 4) COLD WATER LINHE LEAK IN MASTER BATH 5) SECURE TRAP ARM IN MASTER BATH 6) 1" CLEARANCE TO COMBUSTIBLES AROUND FIREPLACE FLU 7) SEAL ALL PENETRATIONS THRU STUCCO |
|
09/22/2005 | FRAMING | Cancelled | IVRS - RI canceled | |
09/21/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONE INCH CLEARANCE FIREPLACE FLUE TO COMBUSTIBLES 2) NO TEST POTABLE H20 3) NO TEST DWV 4) MECH NOT PER PLAN 5) STOPPED INSPECTION |