Permit: T05CM02453

Parcel: 118082230

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/22/2005 FRAMING Approved IVRS - Inspection :*
09/21/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL ITEMS NOT CORRECTED (SUB STILL WORKING)
09/20/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPAIR SHEER AT GARAGE
2) BLOCK MECH STAND
3) FIRE BLOCK CHASE AT WALL CLOSET AND DEN
4) NOT APPROVED TO USE PLUMBERS TAPE TO SUPPORT ABS
5) FIRE BLOCKS MISSING AT KITCHEN
6) FIRE BLOCKS FIRE PLACE
7) SEAL PENETRATIONS FROM 1ST TO 2ND FLOOR
8) STRINGERS MISSING HANGERS DETAIL 9-D2
9) OVER SPANS AT INTERIOR SHEER LIVING ROOM
10) BLKG PANEL MISSING DETAIL 8-D1
11) MECHANICAL NOT PER PLAN