Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM02450
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2005 | FRAMING | Approved | IVRS - Inspection :* | |
09/22/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/21/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) LATH, PENETRATIONS NOT SEALED AND LATH AROUND WINDOWS, NOT COMPLETE AND AROUND ELEC PANEL 2) PARTIAL, MECH NOT PER PLAN (WAITIN ON REVISION) |
|
09/20/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) (LATH) SEAL ALL PENETRATIONS 2) SW2 SHEE MISSING AT GARAGE 3) FIRE BLOCK F/P 4) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR 5) BLOCK REGISTER AT UPSTAIRS BATH 6) FIRE BLOCK STRINGERS 7) WATER LINE NEED 12" CLEARANCE FROM CAN LIGHT 8) MISSING BLOCKING PANEL AT DOWNSTAIRS BED ROOM 9) STRINGERS MISSING HANGERS 10) ST 2115 MISSING PER DETAIL 3D-1 11) MECHANICAL NOT PER PLAN |
|
09/09/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT ELEC IN GARAGE 2) FIRE BLOCK MISSING AT ENTRY CLOSET 3) BLOWN FIRE BLOCK AT DINING ROOM 4) NAIL PROTECT ROMEX FROM OUTSIDE AT DINING ROOM 5) FIRE BLOCK BOTH SIDES OF HOOD VENT 6) SHIM HEADERS 7) FIRE PLACE NOT INSTALLED 8) FIRE BLOCK FIRE PLACE 9) FIRE BLOCK STRINGERS 10) NAIL PROTECT ELECTRIC AT STAIR HAND RAIL STOPPED INSP |