Permit: T05CM02428

Parcel: 11006048D

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
01/17/2006 SHEET ROCK NAILING Approved IVRS - Inspection :*
01/12/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED 5/8" TYPE X SHEETROCK @ BOTH SIDES FOR EACH UNIT @ DEMISING WALL.
2. NEED TO FIRE CAULK ANY PENETRATIONS AND AT JOINTS, EXCEEDING 1/16" IN THICKNESS. USE INTUMESCENT U.L LISTED FIRE CAULK SYSTEM. NEED TO VERIFY SYSTEM LEAVE TUBES ON SITE.
3. CALL FOR RE-INSPECTION NEED TO VERIFY THAT SHEETROCK @ INTERIOR PORTION @ PROPERTY LINES IS 5/8" TYPE X AS WELL