Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2006 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
| 01/12/2006 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED 5/8" TYPE X SHEETROCK @ BOTH SIDES FOR EACH UNIT @ DEMISING WALL. 2. NEED TO FIRE CAULK ANY PENETRATIONS AND AT JOINTS, EXCEEDING 1/16" IN THICKNESS. USE INTUMESCENT U.L LISTED FIRE CAULK SYSTEM. NEED TO VERIFY SYSTEM LEAVE TUBES ON SITE. 3. CALL FOR RE-INSPECTION NEED TO VERIFY THAT SHEETROCK @ INTERIOR PORTION @ PROPERTY LINES IS 5/8" TYPE X AS WELL |